Permit Number: T19CM03595
Parcel: 11942006J

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T19CM03595
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/24/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G1.0 - Index of Drawings - notes sheets a3.0 - Roof Plan ; a6.0 - Wall Sections ; a7.0 - Interior Elevations and Schedules . Sheets a3.0 , a6.0 , a7.0 are not attached to Plan Set. IBC 107.2.1.
2. Sheet G2.0 - 2018 IBC Code Analysis - Sprinkler System : None Required , provide code analysis to support this statement . IBC 107.2.1.
3. Sheet G2.0 - 2018 IBC Code Analysis - Area Seperation : None Required , provide code analysis to support this statement . IBC 107.2.1.
4. Sheet G2.0 - 2018 IBC Code Analysis - Occupancy Seperation ( Table 508.3.3 ) - None Required . No table 508.3.3 in the 2018 IBC , provide code analysis to support this statement . IBC 107.2.1.
5. Sheet G2.0 - Allowable Floor Area - ( Table 503 ) : 9000 S.F. . No table 503 in the 2018 IBC , provide code analysis to support this statement . IBC 107.2.1.
6. Sheet G2.0 - Allowable Height - ( Table 503 ) : 40' , Two Storey . No table 503 in the 2018 IBC , provide code analysis to support this statement . IBC 107.2.1.
7. Sheet G2.0 - Building Elements ( Table 601 ) : 0 HRS , provide code analysis to support this statement . IBC 107.2.1.
8. Sheet G2.0 - Fire Rating at Exterior Walls ( Table 601 ) : >x<5 for group B ; 1 HR Required . Provide complete code analysis of all distances and fire ratings required . IBC 107.2.1.
9. Sheet G2.0 - Allowable Floor Area Increase ( Section 506 ) Increase Not Utilized , provide complete code analysis to support this statement . IBC 107.2.1.
10. Sheet G2.0 - Actual Gross Building Area - Building 1752 Total GSF ( 9000 GSF Allowable ) , provide complete code analysis to support this statement . IBC 107.2.1.
11. Sheet G2.0 - Occupant Load ( Table 1004.1.2. ) . No table 1004.1.2 in the 2018 IBC , provide complete code analysis to support this statement . IBC 107.2.1.
12. Sheet G2.0 - Occupancy Tabulation Per 2012 IBC Table 1004.1.2 . The City of Tucson has adopted the 2018 I -Codes and 2017 NEC , provide correct code information . IBC 107.2.1.
13. Sheet G2.0 - Exit Width Requirement ( Per Table 1005.3.2 ) . No Table 1005.3.2 in the 2018 IBC , provide complete code analysis to support this statement. IBC 107.2.1.
14. Sheet G2.0 - Provide all exit width calculations under Code Analysis illustrating required and provided exits . IBC 107.2.1.
15. Sheet G2.0 - All Facilities Are Within 500 Foot Path of Travel From Any Point In Building ( Section 2902.4.1.) . Provide complete code analysis to clarify and support this statement . IBC 107.2.1.
16. Sheet G2.0 - Provide all plumbing fixture calculations per Chapter 29 2018 IBC and illustrate required and provided fixtures for the proposed building . IBC 29.
17. Sheet G2.0 - "A" Occupancy ( Not Occupied When Other Facilities Are In Use ) , what "A" occupancy , clarify this statement . IBC 107.2.1.
18. Sheet G1.2 - Provide actual , accurate Interior Elevation Details of ADA Bathrooms provided for building and cross reference with building plans IBC 107.2.1.
19. Sheet G2.0 - Illustrate the path of egress travel on plans IBC 107.2.1.
20. Sheet S1.0 - Sheet Index - sheet S1.4 is attached to plan set but not noted in the index . IBC 107.2.1.
21. The Structural Calculations for RCW Classrooms , page 2 references the 2018 IBC under Components and Cladding , but the print outs provided refence the 2012 IBC . IBC 107.2.1.
22. Sheet a1.0 under Wall Types - wall 2A states a single layer 5/8" GWB Interior and 5/8" Exterior GWB Sheathing etc. , the drawing provided has one layer on one side and two layers on the other , please clarify . IBC 107.2.1.
23. Sheet a1.0 - Floor Plan Sheet Legend - Room Name/Number , Door Number , Window Mark , Partition Type - See Sheet Series "X" , but these items are not illustrated in the sheet series "X". IBC 107.2.1.
25. Sheet a2.0 references - 2012 IPC ( Table 1106.2(2) ) Based Upon 3" Rainfall Rate Per Hour - New . The City of Tucson has adopted the 2018 I Codes . IBC 107.2.1.
- Respond to plan review comments in writting .
- Cloud all corrections on plans .
05/31/2019 JPEELDA1 FIRE REVIEW Approved
06/18/2019 LOREN MAKUS ENGINEERING REVIEW Reqs Change DP19-0132 must be approved first.
06/19/2019 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T19CM03595 - New Building (Commercial - Class Room)
Building Plan Review (1st Review) Rincon RV Resort - Accessory use Building
4555 S. Mission Road - RV Zoning

TRANSMITTAL DATE: June 19, 2019

DUE DATE: June 20, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has done a cursory review of the building plans. Prior to a more comprehensive review by zoning the DP must be reviewed and approved prior to zoning approval of the building plans. While the cursory review did yield an indication that the building plans are consistent with a DP that has been submitted for review, zoning cannot approve the building plans at this time.

2. COMMENT: Zoning will review the building plans on the next submittal and do a comparison to the DP if available to assure consistency with what is proposed on the DP drawings as it relates to the zoning review purview (Building footprint, Height, square footage, site conditions etc.). Also zoning cannot approve the building plans until the Commercial Plans reviewer(s) have approved the building plans.

3. COMMENT: If any changes are necessary to the building plans due to plan review comments that affect zoning requirements the DP will have to be revised to reflect the changes. Once the DP is approved by all reviewers and the building plans are approved by the Commercial Plans reviewers zoning can approve the building plans.

4. COMMENT: Clarify what is meant by Educational Shop? It is important to know what the proposed use is in order to do a comprehensive review of the site and how it affects the zoning requirements.

If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: building plans

Final Status

Task End Date Reviewer's Name Type of Review Description
07/16/2019 AMARTIN1 OUT TO CUSTOMER Completed