05/21/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. The City of Tucson has adopted the 2018 International Codes and the 2017 NEC , amend plans with the correct code . IBC 107.2.1.
2. Sheet S5.0 - Sign Support Schedule - Light Pole Pier Footing - proposed pier diameter 24", pier depth 6'-0". The Structural Calculations page 41 of 59 proposes - pier diameter 36", pier depth 4'-10.5" . Please clarify on plan . IBC107.2.1.
3. Sheet S2.1 - Roof Framing Plan - submit structural calculations for the proposed beams - New 3-2"x10" Wood Beam , New 5 1/8" x 12" GLB . IBC 107.2.1.
- Please respond to plan review comments in writting.
- Cloud all revisions on plans .
05/21/2019 MARTIN BROWN FIRE REVIEW Reqs Change Provide correct code edition references
05/28/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify that the specified metering faucet for the public lavatories will be adjusted to dispense a maximum of 0.25 gallons per metering cycle (e.g. 0.5 GPM for 30-seconds). For accessibility, the cycle time must be at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Provide tempered water for the public restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2018.
3. Keynote 6 on sheet P1.0 calls out the relocation of a hand sink and its associated indirect waste receptor; The kitchen drawings identify the sink as a vegetable sink. Clarify the type of sink being relocated. A hand sink requires a direct connection to the grease drain system while a vegetable sink will be indirectly connected. Reference: Section 301.3 and 802.1, IPC 2018. (Hand sinks may be connected to the sanitary drain system only if they are provided with a sign stating: "Handwash sink only! No food preparation or dishwashing allowed." Reference: Section 1003.3, IPC 2018 as amended by the City of Tucson.)
4. Appliances (e.g. soda dispensers, combi-ovens, ice makers, etc.) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.14.1, IPC 2018 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1, 608.3, and 608.17.1, IPC 2018.
05/28/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Demonstrate energy code compliance for the alterations to the building envelope based on the current code (e.g. COMcheck). Reference: Sections C503.1 and C503.3, IECC 2018.
2. Provide a mechanical design and equipment specifications for the installation of the new fryer hood, grease duct, and exhaust fan. The kitchen equipment drawings are essentially shop drawings and are unacceptable in lieu of a mechanical design by an Arizona Registrant. Reference: Sections 107.1 and 107.2.1, IBC 2018.
3. Verify that sufficient make-up air is being supplied to the kitchen. Reference: Sections 508.1 and 508.1.2, IMC 2018.
05/28/2019 ROBERT SHERRY WATER REVIEW Completed
06/13/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide full compliance with the 2012 Tucson/Pima County Outdoor Lighting Code for the exterior luminaires. See section 104 for plan submittal requirements.
2. Provide for Ground Fault protected receptacles in the kitchen and food prep areas. Be advised of the revised article for new requirements in the 210.8B (2), 2017 NEC.
3. Provide complete compliance with the 2018 IECC for lighting energy and controls.
Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC.
06/17/2019 LOREN MAKUS ENGINEERING REVIEW Passed
06/18/2019 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T19CM03538 - Food Service Use / McDonalds Restaurant
Interior Remodel and new two ordering lanes
Building Plan Review (1st Review) - Related to DP19-0122
3105 E. Valencia Road - C-2 Zoning

TRANSMITTAL DATE: June 18, 2019

DUE DATE: June 18, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has reviewed the Building plans for the interior remodel and minor exterior building work. Zoning has no adverse comments to the proposed interior modifications or modifications to the exterior of the building zoning cannot approve the T.I Plans at this review. Zoning cannot approve the building plans until the PDSD Commercial Plans reviewers have approved the building plans.

The building plans include drawings that are applicable to physical site related changes that are under review by PDSD Staff under the development package (DP19-0112) process. The site related plans in the building package must be the approved, stamped and signed copy of the DP sheets or the site sheets must be labeled as "Reference Only see the approved and stamp copy of the DP19-0112". Zoning will review the building plans again on the next submittal.


2. COMMENT: The unapproved version of the DP must be removed from the building package set or they must be stamped as "For reference only see approved and stamped DP18-0297


3. COMMENT: Zoning will review the building plans on the next submittal to assure that any revisions made to the building plans do not affect zoning requirements and that all PDSD commercial plans reviewers have also approved the building plans.


4. COMMENT: On sheet SD-1, detail 8, correct the height dimension of the ADA signs from FFE to the bottom of the lowest sign to show 7'-0".


If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov