Permit Number: T19CM03482
Parcel: 114600830

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM03482
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2019 NICHOLAS ROSS ZONING REVIEW Approved
05/16/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Nail polish is applied at the pedicure stations; provide local exhaust for each pedicure station.
2. The specified 5-on heat pump has a total capacity of 53.9 MBH compared to the calculated total load of 38.7 MBH. Reconcile the difference.
05/16/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide power and controls for exhaust fan #3. Correlate with Mechanical.
Ref; 2017 NEC, 2018 IBC sec 107.2.1,
05/16/2019 NROSS1 ENGINEERING REVIEW Passed
05/16/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1; Partition Types: Please indicate the gauge of the metal studs at walls 4A, 4B, and 6B.
2. Sheet A2; Detail 1: A note indicates 3 5/8" metal studs. Wall 6B is 6" metal studs. Please revise the note.
3. Sheet A2; Details 1 and 2: Please indicate the bracing studs size and gauge, along with the connection size and quantity to the top of the partition and to the structure above.
4. General: Please provide written responses to all review comments.
05/16/2019 ROBERT SHERRY WATER REVIEW Completed
05/16/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
05/16/2019 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/17/2019 JPEELDA1 FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/30/2019 QJONES1 APPROVAL SHELF Completed
05/30/2019 QJONES1 OUT TO CUSTOMER Completed
05/30/2019 QJONES1 REJECT SHELF Completed