Permit Number: T19CM03474
Parcel: 12217002B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM03474
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2019 NICHOLAS ROSS ZONING REVIEW Approved
05/16/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide return grilles for the separate rooms.
2. Provide balancing data for the HVAC system.
3. Show the location of the thermostat.
4. Clarify the data used to determine the ventilation for the suite.
05/16/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide the specifications for the new water heater and expansion tank.
2. Provide a design for the water heater support.
3. Provide water hammer arrestors for the clothes washer.
4. Provide specifications for the water supply valve for the shower.
05/16/2019 NROSS1 ENGINEERING REVIEW Passed
05/16/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/16/2019 ROBERT SHERRY WATER REVIEW Reqs Change Provide the water demand served by the existing 1" water meter.
05/16/2019 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/16/2019 MARTIN BROWN FIRE REVIEW Approved
05/22/2019 PMARTIN1 ELECTRICAL-COMMERCIAL REVIEW Needs Review