Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T19CM03375
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/01/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Comment not resolved. Show the construction of the roof assembly to verify the values used in the COMcheck envelope analysis. Explain where the continuous insulation noted in the COMcheck envelope analysis for the walls and the roof is located. [Initial comment: Provide calculations (e.g. COMcheck) for the building envelope to demonstrate compliance with the energy code; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. As a minimum, the information shall include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2018.] |
07/01/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide calculations to show that the existing restroom facilities provide the minimum plumbing facilities required by Table 2902.1, IBC 2018, for storage occupancy for the entire site. 2. Show the accessible route to the site restrooms to verify that the total travel distance from any point in the storage buildings to restroom facilities does not exceed 500-feet. Reference: Section 2902.3.3, IBC 2018. |
07/06/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. A written response to the electrical plan review comments was requested per the previous plan review. No response for the electrical review comments was located in the re-submittal. 2. It appears the comments were not addressed other that the 2018 IECC for the interior lighting. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/03/2020 | PC_TGUTHEI1 | REJECT SHELF | Passed |
09/03/2020 | PC_TGUTHEI1 | APPROVAL SHELF | Passed |
09/03/2020 | PC_TGUTHEI1 | OUT TO CUSTOMER | Completed |