Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T19CM03375
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/29/2019 | MROSS2 | FIRE | REVIEW | Reqs Change | Please clearly indicate on plans the fire sprinkler supply locations. |
| 06/10/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A0.0; Development Data: The current codes listed should be revised. Remove the word "amendments", and revise all I-Codes to 2018. Remove the IEBC, the Fuel Gas Code, and the Arizona Administrative Code for Swimming Pools. Revise the NEC to the 2017 Edition. 2. Sheet A0.0; Development Data: Please revise the Allowable Area per Table 506.2 of the 2018 IBC. 3. Sheet A0.0; Development Data: The table indicating the ratio of actual square footage only has to be reviewed for 'separated occupancies' (IBC Section 508.4) where individual structures do not meet the required separation distance per the IBC Table 602. Please verify and remove that table as required. 4. Sheet A0.0; Development Data: The table for exit requirements should be revised per the IBC Section 1006.2.1. Please revise the number of required exits. 5. Sheet A0.0; Development Data: The exit requirements references the IBC Section 1019.1. Please revise that reference to the Section in the 2018 IBC. 6. Sheet A0.0; Development Data: The Construction Type is listed as IIB. Please verify that designation per the IBC Section 602.2. 7. Sheet AS101; Project/Data-Code: Please revise this information per Comment 1. 8. Sheets A201 and A202 (Wall Legends); Sheet S109 (Wall Schedule): The Wall Legends on Sheets A201 and A202 indicate the north wall is a W2 Wall Type (4" metal stud at 16" o.c.), while the Wall Schedule on Sheet S109 (and Foundation Plan S201) in the north wall is a W1 Wall Type (6" x 16 ga. metal stud at 16" o.c.). Please coordinate. 9. Sheets A201 and A202 (Wall Legends); Sheet S109 (Wall Schedule): Please verify all walls indicated on Sheets A201 and A202 have stud sizes that coordinate with Sheet S109. 10. Sheet A303; Roof Plan; Building Sections 1/A603 and 2/A603 are cut on this Plan. Sheet A603 Title indicates 'Building 8 Sections'. Please coordinate. 11. Sheet A303; Roof Plan: Keynotes 1 through 4 were not located on the plan. Please revise. 12. Sheets A-501A, A-501B, A-502, and A-503; Exterior Elevations: Please indicate the Elevations on the Floor Plans (Sheets A201 and A202). 13. Sheet A701; Door Types: At the head on two different Door Types, there is no detail indicated. Please revise. 14. Sheet A803: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise. 15. Sheet S001 (Code); Structural Calculations: The drawings and structural calculations indicate the 2012 IBC Code. This permit was applied for after 01-01-2019, therefore requires the 2018 IBC requirements. Please revise and verify all structural requirements for the 2018 IBC are met. 16. Sheet S001; Foundations: Please indicate on this sheet the geotechnical consultant was PRE, Inc., Job #18012. 17. General: Please provide a Special Inspections Certificate with Parts A and B completed. Visit our website at tucsonaz.gov/PDSD. 18. General: Please provide written responses to all review comments. Reviewed by Eric Newcomb Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov |
| 06/20/2019 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | FROM: David Rivera PDSD Zoning Review Section PROJECT: T19CM3373, T19CM3374, T19CM3375 - New Building (Storage Use Group / Personal Storage Building Plan Review (1st Review) Rita Ranch Self Storage 3271 E Valencia Road - C-1 Zoning - Related to DP18-0265 TRANSMITTAL DATE: June 20 DUE DATE: June 21, 2019 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. COMMENT: Zoning has done a review of the building plans. While the review did yield an indication that the building plans are consistent with the approved development package DP18-0265 zoning cannot approve the building plans at this time. 2. COMMENT: Zoning will review the building plans on the next submittal and as it relates to the zoning review purview (Building footprint, Height, square footage, site conditions etc.). Also zoning cannot approve the building plans until the PDSD Commercial Plans reviewer(s) have approved the building plans. 3. COMMENT: If any changes are necessary to the building plans due to plan review comments that affect zoning requirements the DP will have to be revised to reflect the changes. Once the building plans are approved by all PDSD Commercial plan reviewers and the building plans zoning can approve the building plans. If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: building plans |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/26/2019 | AVAUGHN1 | OUT TO CUSTOMER | Completed |