Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM03374
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/04/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
03/12/2020 | DAVID RIVERA | ZONING | REVIEW | Approved | |
03/13/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A0.0; Development Data (Current Codes): Please remove the 2012 International Residential Code. 2. Sheet A0.0; Development Data (Height and Area Analysis): Please revise the reference to the IBC Tables 504.3, 504.4, and 506.2. 3. Sheet A0.0; Development Data (Actual Building Area): Per the IBC Table 506.2, the allowable area for each building is 70,000 SF. Since each building is sufficiently separated from the others, the sum of all three building areas (as indicated on Sheet A0.0) is not required. Please remove the table, and indicate on this sheet each building is allowed 70,000 SF. 4. Sheet AS101; Project/Data-Code: Please remove the 2012 International Residential Code. 5. Sheet AS101; Site Plan: No distance from the west wall of this building to the property line is indicated. Please indicate that distance on the plan, and follow the IBC Table 602 for rated walls. 6. Sheets A203 and A204 (Wall Legends); Sheet S109 (Wall Schedule): The Wall Legends indicate all exterior walls are a W2 Wall Type (4" metal studs at 16" o.c.), while the Wall Schedule (on Sheets S109 and S202) indicate a W1 (6" x 16 gauge metal stud at 16" o.c.). Please coordinate. 7. Sheet A302; Roof Plan: The Building Section is not complete. Please revise. 8. Sheet A302; Roof Plan: Keynotes 1 through 4 were not located on the plan. Please revise. In addition, a Keynote 6 is indicated on the plan but not in the Keynotes. 9. Sheet A603; Sheet Title: Please revise the Sheet Title to "Buildings A and B Sections". 10. Sheet A603; Keynotes: Notes 7 and 8 were not located on the elevations. Please verify. 11. Sheet A603; Building Section: The lower part of the Building Section has a Keynote 6 indicated at the roof. Please remove or add the Keynote. 12. Sheets S202 and S203; Foundation and Framing Plans: The north arrows on these sheets do not match the north arrows on Sheets A203 and A204. Please coordinate. 13. Structural Calculations: Two copies of the Structural Calculations were not included in this submittal. Please provide. 14. General: Please provide written responses to all review comments. |
03/27/2020 | RMCCOY1 | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The Mechanical Compliance Certificate on sheet M401 was designed using the 2012 IECC . The City of Tucson has adopted the 2018 I-Codes . Amend certificate as necessary . IBC107.2.1. |
03/27/2020 | RMCCOY1 | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The Exterior and Interior Lighting Compliance Certificates on sheet E102 are designed with the 2012 IECC , the City of Tucson has adopted the 2018 I-Codes . Amend certificates as necessary . IBC 107.2.1. |
03/27/2020 | RMCCOY1 | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide Code Analysis for the minimum number of required plumbing fixtures , sheet A0.0 . IBC 29. |
04/24/2020 | LBOWERS1 | WATER | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/24/2020 | LBOWERS1 | OUT TO CUSTOMER | Completed |
04/24/2020 | LBOWERS1 | REJECT SHELF | Completed |