Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T19CM03373
Parcel: 141114100

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM03373
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/01/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
07/01/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide calculations to show that the existing restroom facilities provide the minimum plumbing facilities required by Table 2902.1, IBC 2018, for storage occupancy for the entire site.
2. Show the accessible route to the site restrooms to verify that the total travel distance from any point in the storage buildings to restroom facilities does not exceed 500-feet. Reference: Section 2902.3.3, IBC 2018.
07/01/2020 ROBERT SHERRY WATER REVIEW Completed
07/06/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. A written response to the electrical plan review comments was requested per the previous plan review. No response for the electrical review comments was located in the re-submittal.
2. It appears the comments were not addressed other that the 2018 IECC for the interior lighting.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/03/2020 PC_TGUTHEI1 REJECT SHELF Passed
09/03/2020 PC_TGUTHEI1 APPROVAL SHELF Passed
09/03/2020 PC_TGUTHEI1 OUT TO CUSTOMER Completed