Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM03373
Parcel: 141114100

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM03373
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/30/2020 ROBERT SHERRY WATER REVIEW Reqs Change Provide the civil plan referenced on sheet P101 showing the size, route and material of the water service pipe from the water meter to the restroom at building A. The civil plans are also to show the location and size of the reduced pressure backflow assembly and specify the reduced pressure backflow assembly being installed. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf
05/01/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide a specification for EF-1.
2. Correct General Note #7, sheet M101; The controlling code is the 2018 IMC as amended by the City of Tucson..
05/01/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide the civil plan referenced on sheet P101 showing the size, route, and slope of the building sewer and the location of its connection to the public sewer. Reference: Section 107.2.1, IBC 2018.
2. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2018, for storage occupancy.
3. Verify that the total travel distance from any point in the storage buildings to restroom facilities does not exceed 500-feet. Reference: Section 2902.3.3, IBC 2018.
05/20/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/21/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Please revisit the Outdoor Lighting Lumen Calcs, Plan Sheet E101. The data is incorrect.
(a) Per plan sheet A0.0 Project Information Sheet, the parcel size is 4.14 acres, not 5.03 acres. Revise calculations.
(b) Verify that the luminaire lamp color temperature output does not exceed 3500 Kelvin per section 402.1 of the Outdoor Lighting Code (OLC).
2. Ref; Lighting Comcheck needs to be re-vised to the currently adopted 2018 IECC.
3. Show the locations of the electrical breaker panels on the electrical floor plans for each building.
4. Provide GFI protected maintenance receptacles for the mechanical equipment as required pro NEC art 210.63. Buildings A and B.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code.