Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T19CM03373
Parcel: 141114100

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM03373
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/04/2020 MARTIN BROWN FIRE REVIEW Approved
03/12/2020 DAVID RIVERA ZONING REVIEW Approved
03/13/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A0.0; Development Data (Current Codes): Please remove the 2012 International Residential Code.
2. Sheet A0.0; Development Data (Height and Area Analysis): Please revise the reference to the IBC Tables 504.3, 504.4, and 506.2.
3. Sheet A0.0; Development Data (Actual Building Area): Per the IBC Table 506.2, the allowable area for each building is 70,000 SF. Since each building is sufficiently separated from the others, the sum of all three building areas (as indicated on Sheet A0.0) is not required. Please remove the table, and indicate on this sheet each building is allowed 70,000 SF.
4. Sheet AS101; Project/Data-Code: Please remove the 2012 International Residential Code.
5. Sheets A205 and A206 (Wall Legends); Sheet S109 (Wall Schedule): The Wall Legends on Sheets A205 and A206 indicate the south wall (and portions of the east and west walls) indicate a W2 Wall Type (4" metal studs at 16" o.c.), while the Wall Schedule on Sheet S109 (and Foundation Plan S201) is a W1 Wall Type (6" x 16 gauge metal stud at 16" o.c.). Please coordinate.
6. Sheets A601 and A602; Keynotes: There are no Keynotes indicated on the Sections. Please provide.
7. Structural Calculations: Two copies of the Structural Calculations were not included in this submittal. Please provide.
8. General: Please provide written responses to all review comments.
03/27/2020 RMCCOY1 MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The Mechanical Compliance Certificate on sheet M401 was designed using the 2012 IECC . The City of Tucson has adopted the 2018 I-Codes . Amend certificate as necessary . IBC107.2.1.
03/27/2020 RMCCOY1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1. The Exterior and Interior Lighting Compliance Certificates on sheet E102 are designed with the 2012 IECC , the City of Tucson has adopted the 2018 I-Codes . Amend certificates as necessary . IBC 107.2.1.
03/27/2020 RMCCOY1 PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide Code Analysis for the minimum number of required plumbing fixtures , sheet A0.0 . IBC 29.
04/24/2020 LBOWERS1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/24/2020 LBOWERS1 OUT TO CUSTOMER Completed
04/24/2020 LBOWERS1 REJECT SHELF Completed