Review Date Reviewer's Name Type of Review Description Status Comments
12/11/2019 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T19CM3373, T19CM3374, T19CM3375 - New Building (Storage Use Group / Personal Storage
Building Plan Review (2nd Review) Rita Ranch Self Storage
3271 E Valencia Road - C-1 Zoning - Related to DP18-0265

TRANSMITTAL DATE: December 11, 2019


COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has done a review of the building plans. While the review did yield an indication that the building plans are consistent with the approved development package DP18-0265 zoning cannot approve the building plans at this time.

2. COMMENT: Zoning will review the building plans on the next submittal and as it relates to the zoning review purview (Building footprint, Height, square footage, site conditions etc.). Also zoning cannot approve the building plans until the PDSD Commercial Plans reviewer(s) have approved the building plans.

3. COMMENT: If any changes are necessary to the building plans due to plan review comments that affect zoning requirements the DP will have to be revised to reflect the changes. Once the building plans are approved by all PDSD Commercial plan reviewers and the building plans zoning can approve the building plans.



If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: building plans
12/17/2019 MROSS2 FIRE REVIEW Reqs Change Please address comments from previous submital including a response letter indicating how comments were addressed.

1. Please clearly indicate locations of underground fire sprinkler supply locations.
2. Please correct address block to match plan review card.
12/24/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A803: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise.
2. Sheet S001 (Code); Structural Calculations: The drawings and structural calculations indicate the 2012 IBC Code. This permit was applied for after 01-01-2019, therefore requires the 2018 IBC requirements. Please revise and verify all structural requirements for the 2018 IBC are met.
3. Sheet S001; Foundations: Please indicate on this sheet the geotechnical consultant was PRE, Inc., Job #18012.
4. General: Please provide a Special Inspections Certificate with Parts A and B completed. Visit our website at tucsonaz.gov/PDSD.
5. Sheet A601; Keynotes: Notes 4 and 8 were not located on the Elevations. Please verify.
General: Please provide written responses to all review comments.