Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T19CM03358
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/13/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/16/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | The Structural Calculations for Canopy C for the Beam to Column Connection - Plate Thickness specifies a 7/8 inch thick 36 ksi cap plate ; the Plan Set - Sheet S7 - Detail C3 #2 specifies a 3/4 inch by width of beam steel plate . Please clarify on plan . IBC 107.2.1. |
| 06/10/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/12/2019 | QJONES1 | APPROVAL SHELF | Completed |
| 06/12/2019 | QJONES1 | OUT TO CUSTOMER | Completed |
| 06/12/2019 | PMARTIN1 | REJECT SHELF | Completed |