Permit Number: T19CM03327
Parcel: 137055380

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM03327
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/24/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/24/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
06/24/2019 RMCCOY1 ELECTRICAL-COMMERCIAL REVIEW Approved
06/24/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Comment not resolved. The waste and vent riser diagram on sheet P101 has not been revised to show the direct connection of the hand sinks. The northernmost hand sink has a note stating that the vent is to be located below the counter. It is unclear if the vent rises 6" above the flood rim of the hand sink before it runs horizontally. Reference: Section 905.4, IPC 2018. [Initial comment: The hand sinks, B1 and B24 require a direct connection to the sanitary waste system. Reference: Section 301.3, IPC 2018.]