| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/24/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/24/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 06/24/2019 | RMCCOY1 | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/24/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Comment not resolved. The waste and vent riser diagram on sheet P101 has not been revised to show the direct connection of the hand sinks. The northernmost hand sink has a note stating that the vent is to be located below the counter. It is unclear if the vent rises 6" above the flood rim of the hand sink before it runs horizontally. Reference: Section 905.4, IPC 2018. [Initial comment: The hand sinks, B1 and B24 require a direct connection to the sanitary waste system. Reference: Section 301.3, IPC 2018.] |