Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T19CM03327
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/24/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
06/24/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
06/24/2019 | RMCCOY1 | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
06/24/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Comment not resolved. The waste and vent riser diagram on sheet P101 has not been revised to show the direct connection of the hand sinks. The northernmost hand sink has a note stating that the vent is to be located below the counter. It is unclear if the vent rises 6" above the flood rim of the hand sink before it runs horizontally. Reference: Section 905.4, IPC 2018. [Initial comment: The hand sinks, B1 and B24 require a direct connection to the sanitary waste system. Reference: Section 301.3, IPC 2018.] |