Permit Number: T19CM03250
Parcel: 13418113C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM03250
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/08/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter. Reference: Section 406.2, IPC 2018.
2. Provide pressure-absorbing devices for the water connections to appliances equipped with quick acting or solenoid valves (e.g. automatic clothes washers). Reference: Section 604.9, IPC 2018.
3. Medical gas note #11 calls for a "remote shutoff if gases are stored in a remote area." Since the gas storage appears to be in a remote part of the building, do you intend to install a zone valve in the area being revised? Reference: Section 107.2.1, IBC 2018.
05/08/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Show how adequate make-up air is to be provided to the surgical room so that the room pressure remains essentially neutral or only slightly negative without adversely affecting the air balance of the adjacent building areas. Reference: Section 501.4, IMC 2018.
05/08/2019 ROBERT SHERRY WATER REVIEW Completed
05/09/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/15/2019 MARTIN BROWN FIRE REVIEW Approved
06/03/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/06/2019 STEVE SHIELDS ZONING REVIEW Reqs Change Zoning cannot approve until all other PDSD Review Agencies have approved the building plans.