Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM03250
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/08/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter. Reference: Section 406.2, IPC 2018. 2. Provide pressure-absorbing devices for the water connections to appliances equipped with quick acting or solenoid valves (e.g. automatic clothes washers). Reference: Section 604.9, IPC 2018. 3. Medical gas note #11 calls for a "remote shutoff if gases are stored in a remote area." Since the gas storage appears to be in a remote part of the building, do you intend to install a zone valve in the area being revised? Reference: Section 107.2.1, IBC 2018. |
| 05/08/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Show how adequate make-up air is to be provided to the surgical room so that the room pressure remains essentially neutral or only slightly negative without adversely affecting the air balance of the adjacent building areas. Reference: Section 501.4, IMC 2018. |
| 05/08/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 05/09/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/15/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 06/03/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/06/2019 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | Zoning cannot approve until all other PDSD Review Agencies have approved the building plans. |