Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Permit Number - T19CM03227
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/06/2019 | MCASTRO2 | ZONING | REVIEW | Reqs Change | P&DS TRANSMITTAL FROM: Mark Castro, Lead Planner PROJECT: T19CM03227 3455 E Calle Alarcon Cistern TRANSMITTAL: May 6, 2019 COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1). This site is located in the R-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. Within established areas, the minimum required side street perimeter yard is 10 feet measured from the street property line (UDC 6.4.5) Based on a cistern height of 8', the required setback is 10' to the east lot line, proposed is 1'. DDO approval required prior to zoning approval. |
| 05/06/2019 | MCASTRO2 | ENGINEERING | REVIEW | Passed | |
| 05/06/2019 | MCASTRO2 | NPPO | REVIEW | Passed | |
| 05/06/2019 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Passed |