Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T19CM03226
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/23/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet S2.0 - Footing (F) and Anchor Bolt Schedule - footing F3-6 and F5-0 - "T" is 18 inches deep for both ; the structural calculations sheet 18 note DF1 and DF2 at 16 inches deep . Please clarify on plan. IBC 107.2.1. 2. Sheet S4 - Detail 407 does not specify the footing thickness ; provide an accurate description of footing . IBC 107.2.1. 3. Sheet S4.0 Provide descriptions of details 402-410 . IBC 107.2.1. |
| 05/29/2019 | MROSS2 | FIRE | REVIEW | Approved | |
| 06/06/2019 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/10/2019 | PMARTIN1 | OUT TO CUSTOMER | Completed |