05/15/2019 MCASTRO2 ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: Mark Castro
Lead Planner

PROJECT:
T19CM03220
1026 E 26th St
Master Suite, Den & Laundry Addition

TRANSMITTAL: 5/15/19
COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A).

The new closet addition requires a perimeter yard setback of 6' as measured to the west lot line, 3' is proposed.

Based on a wall height of 14' for the master suite addition, the required side perimeter yard setback is 9.24' as measured from the additions to the west lot line, 6' is proposed.

DDO approval required prior to zoning approval.
05/15/2019 MCASTRO2 ENGINEERING REVIEW Passed
05/15/2019 MCASTRO2 NPPO REVIEW Passed
07/05/2019 PMARTIN1 BUILDING-RESIDENTIAL REVIEW Needs Review