Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM03209
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/06/2019 STEVE SHIELDS ZONING REVIEW Approved
05/06/2019 SSHIELD1 ENGINEERING REVIEW Passed
05/06/2019 JPEELDA1 FIRE REVIEW Approved
05/07/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Provide secondary OCPD for the 15 KVA transformer and new panel 2PB. NEC art 408.36B.
05/07/2019 RMCCOY1 MECHANICAL-COMMERCIAL REVIEW Approved
05/07/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/07/2019 RMCCOY1 WATER REVIEW Approved
05/07/2019 RMCCOY1 PLUMBING-COMMERCIAL REVIEW Approved
05/07/2019 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed