Permit Number - T19CM03207
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/08/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 05/16/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/30/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide conduit, conductor sizes and types for the new service secondary's, and feeders from the meter base to the starter enclosure. Ref; 2018 IBC sec 107.2.1, 2017 NEC art 230, 240, 310. |
| 05/31/2019 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
| 06/05/2019 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 07/02/2019 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Approved |