Permit Number: T19CM03181
Parcel: 11711096E

Address:
120 N STONE AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM03181
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/03/2019 ALEXANDRA HINES ZONING REVIEW Approved
05/03/2019 AHINES2 ENGINEERING REVIEW Passed
05/06/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/06/2019 JPEELDA1 FIRE REVIEW Approved
05/06/2019 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/07/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Per 2018 IECC watts per square ft=.79.
2. Provide lighting controls per section C405 2018 IECC.
3. Provide full compliance with the 2012 Tucson/Pima County Outdoor Lighting Code. See sec 104 for plan submittal requirements.
4. Provide a complete one line diagram and panel schedules, service equipment, total load.
Ref; 2017 NEC, 2018 IBC sec 107.2.1, Tucson/Pima County Outdoor Lighting Code.
05/10/2019 QJONES1 MECHANICAL-COMMERCIAL REVIEW Needs Review
05/10/2019 QJONES1 PLUMBING-COMMERCIAL REVIEW Needs Review
05/10/2019 QJONES1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/10/2019 QJONES1 APPROVAL SHELF Completed
05/10/2019 QJONES1 OUT TO CUSTOMER Completed
05/10/2019 QJONES1 REJECT SHELF Completed