Permit Number: T19CM03176
Parcel: 111084910

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T19CM03176
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/10/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change The Plan Index indicates Structural Sheets S-1 , S-2 , S-3 , but S-1 , S-2 , S-3 are not attached to plan set. IBC 107.2.1.
Please respond to plan review comments in writting.
05/10/2019 MASHFOR1 FIRE REVIEW Approved
05/29/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change T19CM03176

1) Update plan set to only reflect the proposed parking canopies. Remove any detail sheets associated with the roof top solar. Update the site plan to either remove the roof top solar or show that the roof top solar is under a separate permit
2) Show on plans all service vehicle maneuvering areas, for waste collection, according to City of Tucson Technical Standards Manual section 8. Show the clear operating space in front of any dumpsters
3) Show on plans any utility easements. It appears that the proposed canopy to the north is directly over a water easement. Adjust positioning of canopies as needed so that they are not located over any easements or obtain written permission from the easement holder for the construction of the canopy


John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
05/30/2019 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T19CM03176 - Parking Lot Solar Canopies
Building Plan Review (1st Review) Condominium Complex
2475 Haskell Drive - O-3 Zoning

TRANSMITTAL DATE: May 30, 2019

DUE DATE: May 30, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: Zoning has reviewed the building plans for the parking lot solar canopies but cannot approve the application at this time. Address the following comments and resubmit.

02. COMMENT: The application includes roof top solar panels and parking lot canopies. Remove the roof top solar panels information from the site plan sheet or label the roof top solar panels as "to be permitted under separate permit application"; remove any details or drawings specific to the roof top panels from the parking lot solar canopies application.

The option is combine the parking lot solar canopy and the Building $1 / #2 roof top solar panels permit applications into one permit application. The parking lot solar canopies and roof top solar panels can then be approved based on approval of the Development Package DP19-0094.

If the permits have intentionally been separated due to timing then remove all details and drawings related to the roof top solar canopy from the parking lot solar canopy application.

03. COMMENT: As of this building plan review The DP has not been approved. The proposed parking lot solar panels along the Valencia Avenue frontage cannot be approved as depicted without approval of a Design Development Option.

04. COMMENT: Zoning will review the parking lot solar canopy application on the next submittal. Zoning will verify if the DDO application is approved and review for any conditions of approval of the DDO on the plans.

05. List as reference the DDO case number next to the title block of the building plans sheets. (A copy of the PDSD approved and stamped Development package shall be provided with parking solar canopy application on the next submittal.)

Label the following on the unapproved version of the site plan sheet, "See the PDSD approved and stamped copy of DP19-0094"

If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
07/03/2019 AMARTIN1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
07/03/2019 AMARTIN1 OIP REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
07/08/2019 AMARTIN1 OUT TO CUSTOMER Completed