Permit Number: T19CM03164
Parcel: 136061560

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM03164
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/23/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The make-up air requirement for a domestic clothes dryer in a closet is to provide an opening of not less than 100 square inches. An 8" diameter flexible duct (50 square inches) and a 10"x 10" EGC5 grille with an open area of 95 square inches is insufficient. [Second comment: Comment not addressed.] [Initial comment: Provide make-up air for the clothes dryer. Reference: Section 504.6, IMC 2018.]
01/23/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
01/27/2020 IMONSHI1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Iman Monshizadeh
PDSD Zoning Review Section

PROJECT: Moose Lodge - T19CM03164
Building Plan (3rd Review)

TRANSMITTAL DATE: January 27th, 2019

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The building plans have been reviewed for compliance with development package DP19-0100 and although it appears that the building plans meet the requirements of DP19-0100 Zoning cannot approve the building plans until the development package has been approved.

3. Until all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Iman.monshizadeh@tucsonaz.gov or (520) 837-4082
02/04/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. The first electrical plan review comments still have not been addressed. The written response included in this 3rd submittal addressed Outdoor Lighting Code. This was never an issue, and is not mentioned in the plan reviewers comments until now. The original Electrical Plan Reviewers comments are as follows;
"Please address the following electrical plan review comments. Also provide a written response.
1. Provide complete electrical service load calcs and other information with the electrical line diagram. See City of Tucson Commercial Plan Submittal Requirements (Electrical). Justify that the service entrance has the capacity for the additional loads and panels 'L1', 'K1', 'M1' ". The existing service rating in amps,voltage, phase, total building load is not shown in the line diagram or plan.
Ref; 2018 IBC sec 107.2.1, 2017 NEC art 220,230, City of Tucson Commercial Plan Submittal Requirements (Electrical). www.tucsonaz.gov/pdsd. Submittal Requirements.
02/11/2020 AMARTIN1 ENGINEERING REVIEW Needs Review