Permit Number: T19CM03127
Parcel: 117143190

Address:
541 S MAIN AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T19CM03127
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/01/2019 MCASTRO2 ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: Mark Castro
Lead Planner

PROJECT:
T19CM03127
541 S Main
SFR Remodel and new additions

TRANSMITTAL: 5/1/19
COMMENTS: the following comments are relative to an application for Historic Review (UDC 5.8.8).

This site is located in the HO-3 zone (UDC 4.7.15). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-3). See Use-Specific Standards 4.9.7.B.6.

The minimum setback is the greater of (10) feet, or (3/4) the height of the structure's wall facing each interior property line (Table 6.3-3.A).

Based on a wall height of 12' for the new garage, the required setback to the south lot line is 10', 0' is proposed.

The minimum setback to the front street perimeter property line is the greater of twenty (20) feet, or one and one-half (1 ½) the height of the proposed wall (UDC 6.4.5.C.1.a).

The required setback for the new porch is 20', proposed is 2'-6" from the front street property lot line.

Historic review required prior to zoning approval.
05/01/2019 MCASTRO2 ENGINEERING REVIEW Passed
05/01/2019 MCASTRO2 NPPO REVIEW Passed
08/08/2019 AVAUGHN1 BUILDING-RESIDENTIAL REVIEW Needs Review