Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T19CM03101
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/27/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Show the conduit routing on the building Interior or exterior. 2. For clarity, correlate the numbers on the line diagram conductors with a schedule or keyed note on the corresponding plans. 3. Include the note requiring a field evaluation for the line side tap on the plan sheets showing the line diagrams also. Ref; 2018 IBC sec 107.2.1, 2017 NEC. City of Tucson Commercial Plan Submittal requirements. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/08/2019 | SBORZAK1 | OUT TO CUSTOMER | Completed |