Review Date Reviewer's Name Type of Review Description Status Comments
09/27/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Show the conduit routing on the building Interior or exterior.
2. For clarity, correlate the numbers on the line diagram conductors with a schedule or keyed note on the corresponding plans.
3. Include the note requiring a field evaluation for the line side tap on the plan sheets showing the line diagrams also.
Ref; 2018 IBC sec 107.2.1, 2017 NEC. City of Tucson Commercial Plan Submittal requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/08/2019 SBORZAK1 OUT TO CUSTOMER Completed