Permit Number: T19CM03101
Parcel: 125111880

Address:
770 N DODGE BL

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T19CM03101
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/09/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Approved
05/13/2019 MARTIN BROWN FIRE REVIEW Approved
05/22/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide electrical plans sealed by an Electrical Engineer registered in the state of Arizona.
2. Ref; Line Side Tap, Plan Sheet E-02. Verify that the bus is marked "TAP" at the PV output interconnection point. Otherwise provide for a field evaluation by an NRTL after the tap is performed to maintain the listing of the equipment.
3. Provide a grounding detail that include the racking system. Also provide listing information from the manufacturer(s).
4. Please provide plans with better resolution for the text. Some of the smaller print is not legible. Due to this issue there may be additional comments at the subsequent review.
Ref; 2018 IBC sec 107.2.1, 2017 NEC.
05/22/2019 TOM WEIDEMAN ZONING REVIEW Completed
05/23/2019 JOHN VAN WINKLE ENGINEERING REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
05/23/2019 TWEIDEM1 APPROVAL SHELF Completed
05/23/2019 TWEIDEM1 OUT TO CUSTOMER Completed
05/23/2019 TWEIDEM1 REJECT SHELF Completed