| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/09/2019 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/13/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/22/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide electrical plans sealed by an Electrical Engineer registered in the state of Arizona. 2. Ref; Line Side Tap, Plan Sheet E-02. Verify that the bus is marked "TAP" at the PV output interconnection point. Otherwise provide for a field evaluation by an NRTL after the tap is performed to maintain the listing of the equipment. 3. Provide a grounding detail that include the racking system. Also provide listing information from the manufacturer(s). 4. Please provide plans with better resolution for the text. Some of the smaller print is not legible. Due to this issue there may be additional comments at the subsequent review. Ref; 2018 IBC sec 107.2.1, 2017 NEC. |
| 05/22/2019 | TOM WEIDEMAN | ZONING | REVIEW | Completed | |
| 05/23/2019 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Passed |