Permit Number: T19CM03070
Parcel: 137055270

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T19CM03070
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/21/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/21/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The new specification for LAV-7 calls for a 0.25 GPM aerator. Verify that the faucet will deliver 0.25 gallons per cycle. [Initial comment: Provide an automatic faucet for the restroom lavatory (LAV-7), dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for at least 10-seconds for accessibility. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.]
06/21/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Show how complying with the client's design standards results in an installation that is at least as energy efficient as would result from complying with the requirements of the 2018 IECC. [Initial comment: Provide justification for installing HVAC units having a total cooling capacity that exceeds the total cooling load shown in the submitted calculations. Reference: Section C403.3.1, IECC 2018.]
2. The storefront glazing will be changing; show that the new glazing complies with the requirements of the 2018 IECC. [Initial comment: Demonstrate energy code compliance for the alterations to the building envelope based on the current code (e.g. COMcheck). Reference: Sections C503.1 and C503.3, IECC 2018.]
07/16/2019 AMARTIN1 ENGINEERING REVIEW Needs Review
07/16/2019 AMARTIN1 BUILDING-COMMERCIAL REVIEW Needs Review