Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T19CM03070
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/21/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
06/21/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The new specification for LAV-7 calls for a 0.25 GPM aerator. Verify that the faucet will deliver 0.25 gallons per cycle. [Initial comment: Provide an automatic faucet for the restroom lavatory (LAV-7), dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for at least 10-seconds for accessibility. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.] |
06/21/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Show how complying with the client's design standards results in an installation that is at least as energy efficient as would result from complying with the requirements of the 2018 IECC. [Initial comment: Provide justification for installing HVAC units having a total cooling capacity that exceeds the total cooling load shown in the submitted calculations. Reference: Section C403.3.1, IECC 2018.] 2. The storefront glazing will be changing; show that the new glazing complies with the requirements of the 2018 IECC. [Initial comment: Demonstrate energy code compliance for the alterations to the building envelope based on the current code (e.g. COMcheck). Reference: Sections C503.1 and C503.3, IECC 2018.] |
07/16/2019 | AMARTIN1 | ENGINEERING | REVIEW | Needs Review | |
07/16/2019 | AMARTIN1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |