Permit Number: T19CM02985
Parcel: 125101410

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM02985
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/29/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/29/2019 MARTIN BROWN FIRE REVIEW Approved
05/01/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Verify that the metering faucets will operate for at least 10-seconds for accessibility and no longer than 30-seconds to limit the water delivery to no more than 0.25 gallons. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
05/01/2019 ROBERT SHERRY WATER REVIEW Completed
05/01/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide heating and cooling load calculations to justify the heating/cooling capacities of the HVAC units, RTU-1 and RTU-2. Reference: Section C403.1.1, IECC 2018.
05/22/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved