Review Details: WALK THRU - COMM

Permit Number - T19CM02916
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/24/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise the building numbers to coordinate with the approved development plan.
2. The installation of 2-way cleanouts is only allowed at the junction of the buildung drain and the building sewer. In addition, the detail is incorrect. Reference: Sections 708.1.3 and 708.1.8, IPC 2018.