Permit Review Detail
Review Status: Completed
Review Details: WALK THRU - COMM
Permit Number - T19CM02916
Review Name: WALK THRU - COMM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/24/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the building numbers to coordinate with the approved development plan. 2. The installation of 2-way cleanouts is only allowed at the junction of the buildung drain and the building sewer. In addition, the detail is incorrect. Reference: Sections 708.1.3 and 708.1.8, IPC 2018. |