Permit Number: T19CM02894
Parcel: 12404102B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM02894
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/09/2019 MARTIN BROWN FIRE REVIEW Approved
05/09/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Verify water heater OCPD with plumbing schedule plan sheet P0.1. Appears to be undersized for 8.32 KW @ 125%= 50 amps.
05/09/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/09/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
05/21/2019 QJONES1 APPROVAL SHELF Completed
05/21/2019 QJONES1 OUT TO CUSTOMER Completed
05/21/2019 QJONES1 REJECT SHELF Completed