Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM02894
Parcel: 12404102B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM02894
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/23/2019 ELISA HAMBLIN ZONING REVIEW Approved
04/23/2019 EHAMBLI1 ENGINEERING REVIEW Passed
04/24/2019 RMCCOY1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change Provide Electrical plans for proposed tenant improvement. 2018 IBC 107.2.1.
04/24/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
04/24/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G0.02; Accessibility General Notes: Note 01 references the 2015 IBC. Please revise to the 2018 Edition.
2. Sheet G1.01; Building Code Matrix (Interior Finishes): A reference is made to interior finishes for a sprinklered condition. Please revise to non-sprinklered.
3. Sheet A10.01; Partition Details: Please indicate the stud gauge and spacing on the details.
4. Sheet A10.01; Partition Details: A note on each detail indicates to see details for bracing. Please provide those details.
5. Sheet A10.01; Partition Details: Is there a reason for Partition Type A indicating a fire resistance rating? Please verify.
6. General: Please provide written responses to all review comments.
04/24/2019 MROSS2 FIRE REVIEW Reqs Change Building is sprinklered. Please change code review analysis to indicate. Include note that sprinklers will be a deferred submittal. Check if alarm system is in building, and indicate.
04/24/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide plumbing design for installation of breakroom sink and dishwasher. Reference: Section 107.2.1, IBC 2018
04/24/2019 ROBERT SHERRY WATER REVIEW Completed
04/24/2019 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed