Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T19CM02863
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/06/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Verify compliance with art 690.11 NEC for the micro Inverters. 2. Provide racking details, grounding, cut sheets for the rooftop arrays. 3. The combined grounding electrode and equipment ground conductor must be sized per 250.166 minimum #8 cu or #6 al. NEC art 690.47 Ref; 2017 NEC. |
| 05/13/2019 | QJONES1 | ENGINEERING | REVIEW | Needs Review | |
| 05/13/2019 | QJONES1 | ZONING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/13/2019 | QJONES1 | APPROVAL SHELF | Completed |
| 05/13/2019 | QJONES1 | OUT TO CUSTOMER | Completed |
| 05/13/2019 | QJONES1 | REJECT SHELF | Completed |