Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM02863
Parcel: 11616287A

Address:
845 N MAIN AV

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T19CM02863
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/06/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Verify compliance with art 690.11 NEC for the micro Inverters.
2. Provide racking details, grounding, cut sheets for the rooftop arrays.
3. The combined grounding electrode and equipment ground conductor must be sized per 250.166 minimum #8 cu or #6 al. NEC art 690.47
Ref; 2017 NEC.
05/13/2019 QJONES1 ENGINEERING REVIEW Needs Review
05/13/2019 QJONES1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/13/2019 QJONES1 APPROVAL SHELF Completed
05/13/2019 QJONES1 OUT TO CUSTOMER Completed
05/13/2019 QJONES1 REJECT SHELF Completed