Permit Number: T19CM02848
Parcel: 12701004H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM02848
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/22/2019 MCASTRO2 ZONING REVIEW Approved
04/22/2019 MCASTRO2 ENGINEERING REVIEW Passed
04/24/2019 RMCCOY1 ELECTRICAL-COMMERCIAL REVIEW Approved
04/24/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
04/24/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet a0.1; Building Codes: Please revise the accessibility code to the 2009 Edition.
2. Sheet a0.2; Exiting Plan: Per the IBC Section 1017.3, the exit access travel distance shall be measured along an unobstructed horizontal and vertical path. Please revise.
3. Sheet a7.0; Section 3: A note indicates to extend the partition to the underside of full height. Please provide a detail for that connection of the partition to the roof.
4. General: Please provide written responses to all review comments.
04/24/2019 MROSS2 FIRE REVIEW Approved
04/24/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/24/2019 ROBERT SHERRY WATER REVIEW Completed
04/24/2019 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed