Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM02848
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/22/2019 | MCASTRO2 | ZONING | REVIEW | Approved | |
| 04/22/2019 | MCASTRO2 | ENGINEERING | REVIEW | Passed | |
| 04/24/2019 | RMCCOY1 | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 04/24/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 04/24/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet a0.1; Building Codes: Please revise the accessibility code to the 2009 Edition. 2. Sheet a0.2; Exiting Plan: Per the IBC Section 1017.3, the exit access travel distance shall be measured along an unobstructed horizontal and vertical path. Please revise. 3. Sheet a7.0; Section 3: A note indicates to extend the partition to the underside of full height. Please provide a detail for that connection of the partition to the roof. 4. General: Please provide written responses to all review comments. |
| 04/24/2019 | MROSS2 | FIRE | REVIEW | Approved | |
| 04/24/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 04/24/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 04/24/2019 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |