Permit Number: T19CM02823
Parcel: 136254100

Review Status: Active

Review Details: COMMERCIAL - TI

Permit Number - T19CM02823
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
04/22/2019 RMCCOY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/22/2019 RMCCOY1 MECHANICAL-COMMERCIAL REVIEW Approved
04/22/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/22/2019 ROBERT SHERRY WATER REVIEW Passed
04/22/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Approved
04/23/2019 JPEELDA1 FIRE REVIEW Approved
04/23/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved Please correlate the electrical requirements for the space heater and exhaust fan with the panel schedule 'HA'. The unit power requirements is 9.8 KW, per mechanical unit cat#. Also provide power for the exhaust fan. See Mechanical plans.
Ref: 2018 IBC sec 107.2.1, 2017 NEC.
04/24/2019 NROSS1 ENGINEERING REVIEW Passed
04/24/2019 NICHOLAS ROSS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/22/2019 ANY APPROVAL SHELF RECEIVED