Permit Number: T19CM02701
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM02701
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/17/2019 ALEXANDRA HINES ZONING REVIEW Approved
04/17/2019 ERIC NEWCOMB MECHANICAL-COMMERCIAL REVIEW Passed
04/17/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please designate a branch circuit and panel for the outlets and show the panel location on the plans.
Provide a complete panel schedule.
Ref: 2018 IBC sec 107.2.1, 2017 NEC
04/17/2019 AHINES2 ENGINEERING REVIEW Passed
04/17/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/17/2019 ENEWCOM1 WATER REVIEW Passed
04/17/2019 ERIC NEWCOMB PLUMBING-COMMERCIAL REVIEW Passed
04/18/2019 MARTIN BROWN FIRE REVIEW Approved