Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T19CM02539
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/11/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide timer for the bathroom exhaust fan. See Mechanical plan for the exhaust fan sequence of operation. Ref; 2017 NEC, 2018 IBC sec 107.2.1, City of Tucson Commercial Plan Submittal Requirements. |
| 09/11/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide a return for each room (see AC-5). Reference: Section 601.2, IMC 2018. |
| 09/17/2019 | QJONES1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/17/2019 | QJONES1 | APPROVAL SHELF | Completed |
| 09/17/2019 | QJONES1 | OUT TO CUSTOMER | Completed |
| 09/17/2019 | QJONES1 | REJECT SHELF | Completed |