Review Date Reviewer's Name Type of Review Description Status Comments
09/11/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet T1.0; Occupancy Group: A revision note indicates this is a business/storage use, while the table indicates a retail. Please coordinate.
2. Sheet T1.0; Occupant Load: Please provide the occupant load for this space. Include the calculation on this sheet.
3. Sheet A2.0; Wall Legend: Wall W2 indicates it is rated per Code. Please indicate the required fire resistance rating, provide the UL number, and provide a detail of that wall on this sheet