Permit Number: T19CM02493
Parcel: 124040010

Address:
1448 E 1ST ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM02493
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/10/2019 NICHOLAS ROSS ZONING REVIEW Approved
04/10/2019 RMCCOY1 MECHANICAL-COMMERCIAL REVIEW Approved
04/10/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. The lumen calcs do not compute. For example, the stated allowed unshielded lumens is calculated at 8140 , the total unshielded lumens used is shown at 50,940 ?
2. Indicate or locate all the new and existing exterior luminaires on the site lighting plan. Section 104.2
Ref; 2012 Tucson/Pima County Outdoor Lighting Code
04/10/2019 NROSS1 ENGINEERING REVIEW Passed
04/10/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Approved
04/10/2019 RMCCOY1 WATER REVIEW Approved
04/10/2019 RMCCOY1 PLUMBING-COMMERCIAL REVIEW Approved
04/10/2019 MARTIN BROWN FIRE REVIEW Approved
04/10/2019 RMCCOY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed