Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM02493
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/10/2019 | NICHOLAS ROSS | ZONING | REVIEW | Approved | |
| 04/10/2019 | RMCCOY1 | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 04/10/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. The lumen calcs do not compute. For example, the stated allowed unshielded lumens is calculated at 8140 , the total unshielded lumens used is shown at 50,940 ? 2. Indicate or locate all the new and existing exterior luminaires on the site lighting plan. Section 104.2 Ref; 2012 Tucson/Pima County Outdoor Lighting Code |
| 04/10/2019 | NROSS1 | ENGINEERING | REVIEW | Passed | |
| 04/10/2019 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/10/2019 | RMCCOY1 | WATER | REVIEW | Approved | |
| 04/10/2019 | RMCCOY1 | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 04/10/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/10/2019 | RMCCOY1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |