Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T19CM02388
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/16/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
05/21/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The Turbochef ventless ovens are listed to UL 710B (KNLZ) and use an internal recirculating catalytic converter to limit smoke, grease and odor emissions. The minimum exhaust rate of 0.70 CFM per square foot based on 100-square feet per appliance is a requirement. (For non-UL 710B listed cooking appliances that do not require a hood, refer to Section 507.3, IMC 2018.) [Initial comment: Spaces in which factory-built recirculating hoods tested in accordance with UL 710B are installed are considered to be kitchens and shall be ventilated per Section 403.3.1.1, IMC 2018. The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Section 507.1, exception 2, IMC 2018.] |
05/21/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The glasswasher note on sheet P3.0 shifts the design responsibility onto the contractor. Determine the temperature of the effluent and specify the appropriate material for the wastewater pipe. Reference: Section 107.1, IBC 2018. [Initial comment: If the discharge temperature of the dishwasher will be greater than 140 degrees Fahrenheit, show that the temperature rating of the drainage pipe material is suitable for the highest temperature of the wastewater. Reference: Section 702.5, IPC 2018.] |
05/29/2019 | QJONES1 | ZONING HC | REVIEW | Passed | |
05/29/2019 | QJONES1 | ZONING | REVIEW | Needs Review | |
05/29/2019 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
05/29/2019 | QJONES1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/29/2019 | QJONES1 | APPROVAL SHELF | Completed |
05/29/2019 | QJONES1 | OUT TO CUSTOMER | Completed |
05/29/2019 | QJONES1 | REJECT SHELF | Completed |