Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2019 MARTIN BROWN FIRE REVIEW Approved
04/09/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheets E2.3 and ES1 are noted in the Index but are not attached with plan set . Please clarify . IBC 107.2.1.
2. Sheet E4.0 is attached with plan set but is not noted in the Index . Please clarify . IBC 107.2.1.
3. Sheets M2.0 and M3.0 are noted in the Index but are not attached with plan set . Please clarify . IBC 107.2.1.
4. Sheets M4.0 and M5.0 are attached to plan set but are not noted in the Index . Please clarify . IBC 107.2.1.
5. Sheet P1.1 is noted in the Index but is not attached with plan set . Please clarify . IBC 107.2.1.
6. Sheet P5.0 is attached with plan set but is not noted in the Index . Please clarify . IBC 107.2.1.

Please respond in writting to all plan review comments .
04/18/2019 ROBERT SHERRY WATER REVIEW Completed
04/18/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify that the specified faucets for the public lavatories are metering faucets that will dispense a maximum of 0.25 gallons per metering cycle and that the cycle time will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Verify that the mixing valve used to supply tempered water to the public restroom lavatories conforms to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2018.
3. Provide backflow protection for the chemical dispenser at the mop sink. Reference: Section 608.3.1, IPC 2018.
4. If the discharge temperature of the dishwasher will be greater than 140 degrees Fahrenheit, show that the temperature rating of the drainage pipe material is suitable for the highest temperature of the wastewater. Reference: Section 702.5, IPC 2018.
5. Revise detail 8/P5.0, which shows a hydromechanical grease interceptor for a 3-compartment sink. The shell building plans called for the installation of a gravity grease interceptor. Reference: Section 107.2.1, IBC 2018 and Section 1003.3, IPC 2018 as amended by the City of Tucson.
04/19/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise General Note N on sheet M1.0 to refer to the ventilation calculations shown on sheet M5.0 and the City of Tucson.
2. Show the size, routing, and termination of the condensate drains. (This was not shown in the shell drawings.) Reference: Section 307.2.1, IMC 2018 as amended by the City of Tucson.
3. Spaces in which factory-built recirculating hoods tested in accordance with UL 710B are installed are considered to be kitchens and shall be ventilated per Section 403.3.1.1, IMC 2018. The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Section 507.1, exception 2, IMC 2018.
4. Show the location for the visible and audible trouble signal from the duct smoke detectors. Reference: Section 606.4.1, exception 2, IMC 2018.
04/29/2019 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT: 65 W River Rd
T19CM02388
Starbuck @ 65 W River.

TRANSMITTAL DATE: April 29, 2019

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The building plan has been reviewed for compliance with development package, DP18-0124, and although it appears that the building plans are compliant with the DP Zoning cannot approve the building plans until all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
05/01/2019 LOREN MAKUS ENGINEERING REVIEW Passed
05/01/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. The lighting calcs for IECC compliance were calculated using the value for retail. Dining/Fast food at .79 watts is better suited for this type of use. Please revise the IECC energy calculations for the lighting. 2018 IECC TABLE C405.3.2(1).
2. Provide for GFI protected receptacles in the food preparation and or kitchen areas. Per 2017 NEC 210.8B (2).
3. The electrical roof plan shows 2 RTU's. The panels schedules show 4. Please clarify.
Ref 2017 NEC, 2018 IBC sec 107.2.1.
05/06/2019 QJONES1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/06/2019 QJONES1 APPROVAL SHELF Passed
05/06/2019 QJONES1 OUT TO CUSTOMER Completed
05/06/2019 QJONES1 REJECT SHELF Completed