| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/11/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comment. Also provide a written response. #1. No compliance with the last electrical plan review comment. The PV inverter output is still connected to the 200 amp service disconnect load end, and also the line side of the service meter, per the 5th plan set line diagram. No change. If this is to be a line side tap, remove the PV inverter output feeder from the tap box and run them straight to the meter enclosure. Ref 2017 NEC art, 690, 705. |