Permit Number: T19CM02329
Parcel: 109250450

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM02329
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/11/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comment. Also provide a written response.
#1. No compliance with the last electrical plan review comment. The PV inverter output is still connected to the 200 amp service disconnect load end, and also the line side of the service meter, per the 5th plan set line diagram. No change. If this is to be a line side tap, remove the PV inverter output feeder from the tap box and run them straight to the meter enclosure.
Ref 2017 NEC art, 690, 705.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/12/2019 TWEIDEM1 APPROVAL SHELF Completed
06/12/2019 TWEIDEM1 OUT TO CUSTOMER Completed
06/12/2019 TWEIDEM1 REJECT SHELF Completed