Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T19CM02329
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/30/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Per telephone conversation between Solar Solutions project manager 'Cause' on 5-15-19, the electrical plan reviewer explained his concerns and code references and it seemed it was understood between both parties. Apparently there was some miscommunication. 2. The line diagrams now show the PV interconnection on load and line side. The Tap must be on either line or load side, but not both, NEC art 705.12. Also review previous comment #1, NEC 690.31B. 3. Provide electrical design and calculations performed by an Arizona registrant who has demonstrated proficiency through registration, education, technical knowledge, or experience to perform such work. 4. This is the forth review, additional plan review fees will be accessed. Ref; 2018 IBC sec 107.2.1, 2017 NEC. |