Permit Number - T19CM02329
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/08/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. The request for more detail in the previous plan review comment #2 was not sufficiently addressed. Please provide the following information: (a) Explain how the 200 amp disconnect is being utilized for the PV interconnection at the electrical service. (b) How are the inverter output feeders terminating in the meter enclosure? Ref; 2017 NEC, 2019 IBC sec 108.2.1 |