Permit Number: T19CM02329
Parcel: 109250450

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T19CM02329
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide electrical plans sealed by an Electrical Engineer registered in the State of Arizona.
2. Provide detailed information including listed materials or equipment for the PV interconnection. If altering the manufacturers design in any way, provide documentation from the manufacturer stating that the proposed tap will not compromise the performance and listing of the service equipment. Otherwise provide for a field evaluation by an NRTL or other approved Agency after the Tap is performed in order to maintain the listing of the equipment. NEC 110.3
3. Provide the ratings of the existing electrical service (Amps, Phase, AIC) and the AC Disconnect.
4. Verify that the inverter has GFI protection as specified per NEC art 690.41B, DC disconnecting means, and provide this information in the plan documents.
5. Provide grounding details for the racking and modules.
6. Provide signage per NEC 690.56C(1).
Ref; 2017 NEC, 2018 IBC sec 107.2.1, City of Tucson Commercial Plan submittal Requirements.
04/11/2019 MARTIN BROWN FIRE REVIEW Approved
04/18/2019 TOM WEIDEMAN ZONING REVIEW Completed
04/18/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Approved
04/19/2019 TOM WEIDEMAN ENGINEERING REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
04/19/2019 TWEIDEM1 APPROVAL SHELF Completed
04/19/2019 TWEIDEM1 OUT TO CUSTOMER Completed
04/19/2019 TWEIDEM1 REJECT SHELF Completed