Permit Number: T19CM02288
Parcel: 12310001C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM02288
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/10/2019 MARTIN BROWN FIRE REVIEW Approved
04/12/2019 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/12/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheets G2.1 through G2.10 (Project Code Summary Occupant Load); Sheets G2.1 through G2.10 (Project Code Summary Exiting Requirements): The Third Level Occupant Load indicates 792, while the Exiting Requirements at the Third Level indicates 783. Please verify and coordinate.
2. Sheet A7.3.22; Sheet Title: Please indicate in the title this is an Enlarged Reflected Ceiling Plan.
3. Sheet A7.3.23; Sheet Title: Please indicate in the title this is Level 3 Interior Elevations.
4. Sheet S2.12.18b; Enlarged Plan 1: A note references 1/S0.6 for a Typical Beam Connection. Please include that sheet in this set.
5. Sheet S2.12.18b; Enlarged Plan 2: A note references 3/S2.12.26 for a Typical Boom Support. Please include that sheet in this set.
6. Sheet S2.12.18b; Enlarged Plan 3: Three notes reference 3/S2.12.26 for a Typical Boom Support. Please include that sheet in this set.
7. Sheet S2.12.18b; Plan View 4: A note references 2/S2.12.26 for a Support Channel Detail. Please include that sheet in this set.
8. Sheet S2.12.18b; Plan View 4: A detail references 1/S2.12.26 for a C12 Connection. Please include that sheet in this set.
9. Sheet S2.12.18b; Section 6: A detail references 5/S2.12.26 for a Tube Connection. Please include that sheet in this set.
10. Sheet S2.12.18b; Section 6: A detail references 12/S2.12.27 for a Unistrut Connection. Please include that sheet in this set.
11. General: Please provide written responses to all review comments.

Reviewed by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
04/16/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
04/16/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
04/16/2019 ROBERT SHERRY WATER REVIEW Completed
04/25/2019 DAVID RIVERA ZONING REVIEW Approved
04/29/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Ref; Plan Sheet E1.4.9. Provide a feeder schedule for feeder C08-4.
2. Ref; Plan Sheets E3.3.4, E4.3.3, E4.3.4, E6.3.3, E6.3.4. All the areas are using the same detail, E8.3.4. The room floor plan layouts do not seem to match. Please clarify.
3. Ref; Plan Sheet E8.3.4. See General Notes. The branch circuit panels are not called out.
Ref: 2018 IBC sec 107.2.1, 2017 NEC.
05/02/2019 JOHN VAN WINKLE ENGINEERING REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
05/08/2019 TWEIDEM1 APPROVAL SHELF Completed
05/08/2019 TWEIDEM1 OUT TO CUSTOMER Completed
05/08/2019 TWEIDEM1 REJECT SHELF Completed