Permit Number: T19CM02180
Parcel: 12810076A

Review Status: Completed

Review Details: 3RD PARTY REVIEW - COMMERCIAL TI

Permit Number - T19CM02180
Review Name: 3RD PARTY REVIEW - COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/04/2019 MARTIN BROWN FIRE REVIEW Reqs Change 2nd floor occupant load calculated at 1/150 (sheet A1.1).
Per table 1004 of the 2018 IFC, B occupancies should be calculated at 1/100. Please clarify.
Per section 907.2.2, B occupancies with more than 100 above the lowest level of exit discharge require a fire alarm.
Please indicate on plans that sprinklers and alarms will be deferred submittals.
04/24/2019 ROBERT SHERRY WATER REVIEW Completed
04/25/2019 DAVID RIVERA ZONING REVIEW Approved
05/01/2019 LOREN MAKUS ENGINEERING REVIEW Passed
06/19/2019 PMARTIN1 ADA REVIEW Approved
06/19/2019 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
06/19/2019 PMARTIN1 OUT TO CUSTOMER Completed