Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/04/2019 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | 2nd floor occupant load calculated at 1/150 (sheet A1.1). Per table 1004 of the 2018 IFC, B occupancies should be calculated at 1/100. Please clarify. Per section 907.2.2, B occupancies with more than 100 above the lowest level of exit discharge require a fire alarm. Please indicate on plans that sprinklers and alarms will be deferred submittals. |
04/24/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
04/25/2019 | DAVID RIVERA | ZONING | REVIEW | Approved | |
05/01/2019 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
06/19/2019 | PMARTIN1 | ADA | REVIEW | Approved | |
06/19/2019 | STANTEC | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Completed |