Permit Number: T19CM02108
Parcel: 10408092B

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T19CM02108
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/09/2019 MARTIN BROWN FIRE REVIEW Approved
04/10/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise the roof drainage calculations for the north addition by including half of each surrounding vertical parapet (for the existing and for the addition). Reference: Section 1106.4, IPC 2018.
2. Recalculate the size of the new scuppers based on roof area each is draining (i.e. the area bounded by the high points of the crickets), the vertical walls, and the contributing drainage from the existing roof. Reference: Sections 1101.7, 1106.2, and 1106.4, IPC 2018.
3. Provide secondary roof drainage per Section 1108, IPC 2018.
4. Clarify the design of the downspout manifold, including the slope of the horizontal member. Reference: Section 1106.2, IPC 2018.
04/10/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
04/11/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide energy code compliance calculations (e.g. COMcheck) for the additions to the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the additions to the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation. Reference: Sections C402, C502.1, International Energy Conservation Code 2018.
04/15/2019 AMARTIN1 ENGINEERING REVIEW Needs Review
04/15/2019 AMARTIN1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
04/15/2019 AMARTIN1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/15/2019 AMARTIN1 OUT TO CUSTOMER Completed